Insulation Quality Analyzer
Insulation analysis within wide range
The Sonel MIC-15K1 insulation resistance meter has been
designed to
measure insulation resistance of electrical power engineering
objects, including single and multi-core cables, transformers,
motors and generators, condensers, circuit breakers and other power
station equipment. It is especially recommended for measurements in
areas with very high electromagnetic disturbances, e.g. at
substations with a voltage of 1200 kV AC or 500 kV DC. Due to the
measuring voltage of 15 kV (in accordance with the guidelines of
ANSI/NETA ATS-2009 TABLE 100.1 standards) the meter can be used for
objects with nominal voltage above 34.5 kV.
The MIC-15k1 is an extremely modern, ergonomic device with intuitive
operation. It will satisfy even the most demanding measuring
engineers in the most difficult conditions, with large disturbances,
where other meters will be useless.
MIC-15k1 meter is designed to measure insulation resistance of power objects, i.e.:
It is especially recommended for measurements in areas with very high electromagnetic disturbances, e.g. electrical substations with 1200 kV AC and 800 kV DC. Thanks to the 15 kV measuring voltage (in accordance with ANSI / NETA ATS-2009 TABLES 100.1) the meter can be used for measuring objects with a nominal voltage above 34.5 kV.
Highly efficient
HV inverter, with test voltage of 15 kV and
current up to 10 mA, suitable for measuring the insulation
resistance up to 40 TΩ.
Achieving such a result makes these meters unrivalled devices.
Three-wire resistance measurement, performed using a "GUARD" wire,
eliminates surface
leakage currents caused by contaminated insulation, thereby
increasing the reliability of obtained results.
The meter indicates the Dielectric Absorption Ratio DAR,
Polarization Index PI and the value of Dielectric
DischargeDD.
The device allows user to assess the condition of the insulation, by
applying the test voltage incrementally in steps (SV - Step Volatge)
or smoothly (RampTest - RT).
Built-in digital filters, with averaging time of 10, 30, 60, 100, 200 sec. guarantee stable measurement results in areas of strong electromagnetic interference
A very useful solution is the function that allows to Burnout the damaged object. In case of exposed cables, it enables visual identification of the fault location. In the case of shielded cables, the method allows to generate a seismicacoustic wave from the place of damage. In special conditions, an energetic discharge will appear cyclically. By using the geophone it will be possible to precisely pinpoint the place where such a discharge occurs. Burnout feature allows also locating transient faults (appearing, for example, only during rainfall) with the support of reflectometry, and in case of a short circuit (of a screen or return wire) to the ground - applying the method of measuring voltage drop (the A-frame).
The device automatically saves the measurement results. The number of autosave points depends on the amount of data, which is saved within the main memory.
The Sonel MIC
Mobile mobile app allows to observe the results
during the measurement. The application can generate real-time
graphs
in various configurations. This allows to evaluate the condition of
the object already during the tests.
The option of remote start and stop of the measurement is
particularly useful. Thanks to it, the tests can be carried
out remotely, eg.
from a different room or inside the car, when there are difficult
weather conditions for the user. Using the phone GPS, it is possible
to
precisely determine the place of measurement.
Thanks to the mobile application and the Sonel Reader
software, the user can store previous measurements data and compare
them with current results
transferred from the meter's extensive memory. This solution allows
to prepare a measurement report, track the progress of insulation
degradation
and plan renovation works.